APC Smart-UPS SRT 10000 – "Power Sys Error-02000", inverter fault, UPS dropped output. Repair or replace?

Our SRT 10000 (2018, UPS fw 04.7, NMC2 6.5.6) had an inverter fault today. It went to bypass for about 50 minutes, then dropped the output completely. LCD just said "Power Sys Error-02000", no extra sub-code. NMC log only shows the generic "inverter fault exists" (0x0165). I cleared the error and turned the output back on. Self-test passes and it's running fine for now. One thing worth mentioning: our input power has been bad lately. It's been going to battery 2-4 times a day on low voltage / distorted input, so the inverter has been getting a workout. Anyone been through this? Did it come back, or was it the start of the end? It's out of warranty, so I'm leaning towards replacing it, but

…